Cooper Bussmann FRN Series Brass 50 Amp 250-Volt Fusetron Time Delay Fuse

Item # 2487626 | Cooper Bussmann Part # FRN-R-50 | UPC Code 051712101806 | UNSPSC Code 39121600 | Catalog Page #1086
Add to Favorites List Add to Customized Product Offering Remove From Customized Product Offering Add To Bin Labels Added to Bin Labels. Click icon to print Bin Labels. Add To Custom Catalog Added To Custom Catalog. Click icon to print Custom Catalog. Email Print

Product Overview

The RK5 fuse provides motor overload, ground fault and short-circuit protection. Helps protect motors against burnout from single phasing on three phase systems. Simplifies and improves blackout prevention (selective coordination). Dual-element fuses can be applied in circuits subject to temporary motor overloads and surge currents to provide both high performance short-circuit and overload protection. The overload element provides protection against low level overcurrent of overloads and will hold an overload which is five times greater than the ampere rating of the fuse for a minimum of ten seconds.

  • 50 Amp
  • 250-Volt
  • UL Listed
  • High SCCR

Documentation

Specifications

Certifications and Listings
CSA Certified, UL Listed
Manufacturer Warranty
None
Material
Brass
Maximum Amperage
50, 50 amp
Pack Size
10, 5 Pack or More
Product Depth (in.)
.81
Product Diameter (in.)
0.81
Product Height (in.)
3.0
Product Length (in.)
3
Product Weight (lb.)
0.12
Product Width (in.)
0.81
Voltage
250, 250 volts
Certifications
UL

Warranty

None